To prevent damage during transportation, products are pallet-wrapped. Components are packaged in a way that prevents them from damaging each other. Wooden spacers are placed between panels and formed parts, and then secured with steel straps. This also prevents the pallet from coming apart.

Tank installation and after-sales services are carried out by our experienced technicians.

Our products are delivered fully completed, having undergone all safety and quality tests.

Once installation is completed, the tank’s piping connections are made and it is filled with water. If no water loss occurs, the testing process is considered complete.

 

The required foundation dimensions for tank installation should be prepared as shown below and must be ready prior to installation.

BASE DIMENSIONS

TANK TYPE

BASE DESIGN

BASE DIMENSI ONS

BASE LEVEL TOLERANCE

GRP

BASE WITH INTERNAL FLANGES

FLAT CONCRETE BASE

INTERNAL DIMENSIONS + 200 mm

2 mm per 6 m.

BASE WITH EXTERNAL FLANGES

1 m CENTERED STEEL/CONCRETE SUPPORTS

INTERNAL DIMENSIONS + 200 mm

2 mm per 6 m.

1080 MODÜLER

All

FLAT CONCRETE BASE

INTERNAL DIMENSIONS + 0 mm

2 mm for every 6 m.

1220 MODÜLER

BASE WITH INTERNAL FLANGES

FLAT CONCRETE BASE

INTERNAL DIMENSIONS + 300 mm

±3 mm per 1 m.

BASE WITH EXTERNAL FLANGES

1.22 m CENTERED STEEL/CONCRETE SUPPORTS

INTERNAL DIMENSIONS + 300 mm

±3 mm per 1 m.

MINIMUM INSTALLATION CLEARANCE REQUIRED AROUND THE TANK

TANK TYPE

Tank height IncludIng the base < 2.5 m

Tank heIght including the base > 2.5 m

aBOVE THE TANK

UNDER THE TANK

If scaffoldIng is to be Installed.

TOWER HEIGHT

BASE WITH INTERNAL FLANGES

BASE WITH EXTERNAL FLANGES

GRP

External dimensions + 500 mm

External dimensions + 750 mm

External dimensions + 850 mm

500 mm

0

500 mm

1080 Modular

External dimensions + 500 mm

External dimensions + 750 mm

External dimensions + 850 mm

500 mm

0

500 mm

1220 Modular

External dimensions + 500 mm

External dimensions + 750 mm

External dimensions + 850 mm

500 mm

0

500 mm